Owner's manual

Monitoring and Troubleshooting 5-5
1503-UM051D-EN-P – June 2013
Table 5.C – Module Troubleshooting (cont.)
Problem or Trip Indicated Indication of the following conditions Possible Solutions
Motor Protection activated Investigate and reset.
Stop command initiated Verify circuit
Module Status LED ‘Red’ Undervoltage fault (no TDUV), control voltage
dipped below trip point. Cycle control power
to reset. Verify voltage levels are 110 to 240
VAC, 110 to 250 VDC.
With external capacitor and TDUV feature
activated, undervoltage condition for longer
than programmed TDUV time. Undervoltage
fault activated. Cycle control power to reset.
Module Status LED ‘Green’ and Contactor
Status LED ‘Red Flash 2’ (Series B only)
Contactor Status feedback between Terminals
11 and 12 on the IntelliVAC has closed. The
IntelliVAC will de-energize the coil, thinking
the contactor has opened for other reasons.
Contactor opens during operation
Both status LEDs ‘Off’ Check control voltage and internal control
fuse. (Refer to Figure 4.1 for location.)
Module Status LED ‘Red’ and Contactor
Status LED ‘Yellow’ (Series A, with firmware
2.001 or newer)
Check control power to ensure that it has not
dipped below minimum (see Table 5.D).
Contactor does not open
(mechanical latch only)
Module Status LED ‘Yellow’ and Contactor
Status LED ‘Yellow’ (Series B, with firmware
2.001 or newer)
Trip mechanism is damaged. Inspect and
replace if needed.
Check for loose connections in the control
circuit.
Refer to Tables 5.A or 5.B for definition of Module LED states.
Table 5.D – Minimum IntelliVAC Operational Supply Voltages
Voltage Level
Contactor Rating
(Amps)
Minimum Voltage
(VAC, 47 to 63 Hz)
Pick-Up 400/800 95
Drop-Out 400/800 75
400 70
Trip (Mechanical Latch)
800 80