Owner's manual

5-4 Monitoring and Troubleshooting
1503-UM051D-EN-P – June 2013
Table 5.C – M
odule Troubleshooting
Problem or Trip Indicated Indication of the following conditions Possible Solutions
Motor Protection activated
Both Status LEDs ‘Off’
• Investigate and reset
Check Control Power
Loose connections in control circuit
Verify IntelliVAC power input plug is in place
and properly seated
Verify internal control fuse has not opened
(Refer to Figure 4.1 for location)
Module Status LED ‘Red’ upon power up
(Series A)
IntelliVAC faulted. Cycle control power to
reset. Replace IntelliVAC if unsuccessful.
Module Status LED ‘Red’ upon power up
(Series A)
Module Status ‘Red Flash 1’ upon power up
(Series B)
Improper setting of dip switches. Check
settings and cycle control power.
Contactor does not energize
Loose connection in control circuit. Verify contactor auxiliary set up. Reference
Publication 1502-UM052A-EN-P (400A) or
1502-UM051B-EN-P (800A) – Auxiliary
Contact Set-up Procedure.
Verify circuit continuity (is contactor plug
connected properly?)
Module status LED ‘Red’ and Contactor
Status LED ‘Off’ (Series A)
Coil damaged or connections are loose.
Repair and cycle control power.
Auxiliary Contact Assembly improperly
adjusted. Reference Publication 1502-
UM052A-EN-P (400A) or 1502-UM051B-EN-P
(800A) – Auxiliary Contact Set-up Procedure.
Cycle control power to reset.
Undervoltage fault (no TDUV), control voltage
dipped below trip point. Cycle control power
to reset. Verify voltage levels are 110 to 240
VAC, 110 to 250VDC
Module status LED ‘Red’ and Contactor
Status LED ‘Off’ (Series A)
Module status LED ‘Green’ and Contactor
Status LED ‘Red Flash 1’ (Series B)
Armature Plate obstructed from closing to coil
face. Verify no foreign material behind the
armature plate. Cycle control power to reset.
Contactor closes momentarily and
will not reclose.
Both status LEDs ‘Off’ Check internal control fuse. Verify IntelliVAC
operation in test mode before applying Medium
Voltage. (Refer to Fig. 4.1 for location.)