Owner's manual
4-2 Setup and Commissioning
1503-UM051D-EN-P – June 2013
IntelliVAC units shipped in a complete MV controller (Bulletin
1500/1900) will be configured to suit the installed application (i.e.
contactor type). The user should verify the settings before energizing
the equipment. Table 4.B defines the settings for each switch.
UP = 1
DOWN = 0
DIP switch SW1
1 2 3 4 5 6 7 8 9 10 11 12
| | | |
Altitude X
1 2 3 12
Power-Up Safety Y
-1000 to 0
0 0 0 0
Enable
1 to 1000
0 0 1 1
Disable
1001 to 2000
0 1 0
2001 to 3000
0 1 1 10 11
Ext. cap. TDUV time
3001 to 4000
1 0 0 0 0
0.2 sec
4001 to 5000
1 0 1 0 1
0.5 sec
Not defined
1 1 0 1 0
1.0 sec
Not defined
1 1 1 1 1
2.0 sec
9
TDUV config.
0
No TDUV
Drop out time Z
4 5 6 1
TDUV Enabled
50 msec
0 0 0
75 msec
0 0 1 7 8
Contactor Config.
100 msec
0 1 0 0 0
400A Mech. Latch
130 msec
0 1 1 0 1
400A Elec. Held
150 msec
1 0 0 1 0
800A Mech. Latch
175 msec
1 0 1 1 1
800A Elec. Held
200 msec
1 1 0
240 msec
1 1 1
X The altitude compensation by DIP switch settings applies to Series E 400 amp vacuum contactors only. All 800 amp contactors are adapted
for altitude by altering the return springs. 800 amp contactors are to be set for 1 to 1000m (001 DIP setting).
Y Available with IntelliVAC using version 2.001 firmware or newer.
Z By-pass contactors in MV SMC applications must be set for 50 millisecond drop-out time.
Refer to Appendix A for typical drop-out time settings used when power fuses are provided by Rockwell Automation.
IntelliVAC Configuration
(cont.)