Owner's manual

3-18 Installation and Wiring
1503-UM051D-EN-P – June 2013
Time Delay Undervoltage The IntelliVAC can be configured to provide time delay undervoltage
(TDUV) protection. The feature is available to keep electrically held
contactors closed during a voltage dip or brief power loss. This
option may require the addition of a capacitor (see below). Refer to
Chapter 6 for typical capacitor sizing. The capacitor is connected to
terminals 1(-) and 2(+) of the IntelliVAC. (Refer to Figure 3.15.)
Table 4.B of the “Setup and Commissioning” chapter has the dip
switch settings to provide TDUV from 0.2 to 2 seconds. IntelliVAC
can provide TDUV protection without the use of an external
capacitor, as shown in Table 3.D.
Table 3.D – Maximum TDUV Time (without Capacitor)
Control Voltage Max. TDUV Time (secs)
110/120 V 0.2
220/240 V 1.0
The following conditions will initiate TDUV protection, regardless
of the supply voltage:
1. If the supply voltage drops below 90 VAC/VDC after the first
200 milliseconds after a contact close request.
2. When the supply voltage drops below 72 VAC/FDC after the
200 millisecond close sequence.
If the undervoltage condition persists beyond the set delay time, the
contactor will be opened and an undervoltage fault condition will occur.
Refer to Table 3.A for recommended fuse sizing.
N'
N
EMC FILTER
G
P'
P
MOV
32
1
EC
-
+
4
TCO
12
11
AUX CCO
5
6
L1 L2/NG
+-
STOP
START
OVERLOAD
CONTROL
POWER
FUSE
*
CONTROL POWER
M-IV
910
CLOSE
M-IV
15 16
CONTACTOR
STATUS
M
M-IV
M
CAPACITOR
Refer to Table 3.A for recommended fuse sizing.
N'
N
EMC FILTER
G
P'
P
MOV
32
1
EC
-
+
4
TCO
12
11
AUX CCO
5
6
L1 L2/NG
+-
STOP
START
OVERLOAD
CONTROL
POWER
FUSE
*
CONTROL POWER
M-IV
910
CLOSE
M-IV
15 16
CONTACTOR
STATUS
M
M-IV
M
CAPACITOR
Figure 3.15 – TDUV Control Circuit