User Manual

4-20 Maintenance
1502-UM051E-EN-P – June 2013
Drop-out Time Conversion Series D
eaveragenormaldrop-outtimeforthecontactoris200ms.e"fastdrop-
out"contactorhasadrop-outtimelessthan60ms.Conversionfrom"normal"
to"fast"orvice-versaiseasilyachievedbychangingthecontrolcomponentwired
inparallelwiththeclosingcoil(seeFigures3.3and3.4).erequiredcompo-
nentscanbeorderedfromRockwellAutomationandinstalledpertheappropri-
ate schematic.
Normal drop-out parts:
(1) Rectierbridge 24808-451-01
(1) Mountingscrew M-8765
(1) Wireassembly 80018-457-32
(1) Wireassembly 80018-457-33
Fast drop-out parts:
(1) MOVassembly 80145-581-03
erectierbridgeforthenormaldrop-outmountsontheoutsideofthele
sideplateabovetheauxiliaryassembly(mountingholeprovided).eMOVfor
thefastdrop-outmountsdirectlyontheterminalblocksasshowninFigures
4.15and4.16.
Series E
Contactordrop-outtimesaresetwithinandcontrolledbytheIntelliVACor
IntelliVACPluscontrolmodules(refertopublications1503-UM053_-EN-Por
1503-UM054_-EN-P).