ReferringtoFigure4.18forSeriesDorFigure4.19forSeriesEmechanical-
ly latched contactors,connecttheleadsfromthecoiltotheterminalblock
assemblyasfollows:
Series D: • Closingcoil(yellowlead)to"H1"
• Closingcoil(blacklead)to"H2"
• Hold-incoil(yellowlead)to"C1"
• Hold-incoil(bluelead)to"C2"
• TripCoil(whitelead)to"D"
• TripCoil(bluelead)to"B"
Series E: • Closingcoil(yellowlead)to"C"
• Closingcoil(blacklead)to"A"
• TripCoil(whitelead)to"D"
• TripCoil(bluelead)to"B"
Note: econtactorwillhaveeitherahighdensity(1492-HC6)oraregular
(1492-HJ86)terminalblock.ewiringconventionisthesameforbothtypes.
Hold -in coil (blue lead)
MOVs
Hold -in coil (yellow lead)
Closing coil (black lead)
Closing coil (yellow lead)
Figure 4.15 – Terminal Block Assembly (Electrically held Series D Contactor,
regular terminal block)
Hold -in coil (blue lead)
MOVs
Hold -in coil (yellow lead)
Closing coil (black lead)
Closing coil (yellow lead)
Figure 4.16 – Terminal Block Assembly (Electrically Held Series D Contactor,
high density terminal block)
Note: Figures 4.15 and 4.16 show the fast drop-out
conguration. The normal drop-out contactor has only
one (1) MOV.