User Manual

Rockwell Automation Publication 1502-UM052H-EN-P - June 2013 55
Chapter 5
Troubleshooting
Troubleshooting and
Contactor Coil Resistance
If an operating problem occurs, use the following troubleshooting chart to isolate
the cause of the failure and find corrective action. If the corrective action fails to
resolve the problem, consult your local Rockwell Automation field support
representative.
If faulty contactor coil(s) are the suspected cause of malfunction, refer to Table 7
for typical coil resistance values and check the contactor coils.
(1) Resistance values listed have a tolerance of ±10%. Refer to page 17 for measurement points at the contactor receptacle.
(2) Supplied only with mechanical latch option.
Table 6 - Troubleshooting
Symptom Possible Cause Actions
Contactor Chatters
(1)
Loose connections in control circuit
Coil leads reversed
Control voltage too low
Foreign material on contactor magnet
Improper set-up of contactor auxiliary contact
assembly
Faulty auxiliary contacts
Faulty CR1 or CR2 interposing relay (mechanical latch
only)
Faulty IntelliVAC or IntelliVAC Plus
Latch not engaging
Check all connections in control circuit for tightness
Check wiring from the coil to the terminal block
assembly
Measure control voltage. Refer to Contactor
Specifications for minimum pick-up voltage
Clean magnet cores and armature
Check set-up of contactor auxiliary contact assembly.
Check master contact cartridges on contactor
Ensure N.C. contact from contactor auxiliary assembly
is wired to auxiliary input on IntelliVAC or IntelliVAC
Plus
Replace IntelliVAC or IntelliVAC Plus control module
Check adjustment of mechanical latch
Coil Burnout Coil leads improperly wired
Faulty IntelliVAC or IntelliVAC Plus control module
(2)
Improper set-up of contactor auxiliary contact
assembly
(1)
Control voltage too high
(2)
Check wiring from the coil to the terminal block
assembly
Replace IntelliVAC or IntelliVAC Plus control module
(2)
Check set-up of contactor auxiliary contact assembly
(1)
Check for correct control voltage
(1)
Contactor does not energize Loose connections in control circuit
Damaged contactor auxiliary contacts
Control voltage too low
Improper set-up of contactor auxiliary contact assembly
Faulty CR1 or CR2 interposing relay
(1)
Faulty IntelliVAC or IntelliVAC Plus control module
(2)
Check all connections in control circuit for tightness.
Check wiring from the coil to the terminal block
assembly
Replace contactor auxiliary contact assembly
Measure control voltage. Refer to Contactor
specifications for minimum pick-up voltage
Check set-up of contactor auxiliary contact assembly
Check CR1 and CR2 relay
(1)
Check IntelliVAC or IntelliVAC Plus status LEDs
(2)
(1) Valid if mechanical latch contactors are controlled with electromechanical circuit only.
(2) Valid if IntelliVAC or IntelliVAC Plus control module is used (refer to 1503-UM053_-EN-P
and 1503-UM054_-EN-P).
Table 7 - Typical Contactor Coil Resistance Values
Coil Part Number Description DC resistance (Ω)
(1)
80026-230-01 Operating Coil (each) 19.2 (9.6 x 2)
80022-067-01
(2)
Mechanical Latch Trip Coil 17.6