User Manual
2-2 Equipment Description
1500-IN059C-EN-E – June 2013
Operational Requirements
(cont.)
GE Multilin
Function Description
169/269/269 Plus 369
Bul. 825 Plus
Parameters
Jam Protection Yes Yes Yes
Undervoltage Protection Yes (w/metering option) Yes (w/metering option) Yes
Ground Fault Alarm Current 1 – 10 A 0.25 – 25 A 0.01 – 25 A
Ground Fault Trip Current 1 – 10 A 0.25 – 25 A 0.01 – 25 A
Ground Fault Trip Delay Time 1 – 255 s 0 – 255 s 0 s – 5 s
Short Circuit Protection Yes Yes Yes
Jam Circuit Current 1.5 – 6 (multiple of FLC) 1 – 6 (multiple of FLC) 1 – 6 (multiple of FLC)
Underload Trip Current 1 – 1000 A 10 – 99 (percent of FLC) 10 – 100 (percent of FLC)
Underload Trip Time Delay 1 – 255 s 1 – 255 s 1 – 120 s
Ultimate Trip Current 4 – 12 (multiple of FLC) 2 – 20 (multiple of FLC) 4 – 12 (multiple of FLC)
Winding Alarm Temperature 0 – 200°C 1 – 200°C 0°C – 200°C
Winding Trip Temperature 0 – 200°C 1 – 200°C 0°C – 200°C
Bearing Alarm Temperature 0 – 200°C 1 – 200°C 0°C – 200°C
Bearing Trip Temperature 0 – 200°C 1 – 200°C 0°C – 200°C
Ambient Temperature Sensor Input No Yes Yes
Reset Condition Auto / Manual Auto / Manual Auto / Manual
Speed Switch Input
169/269 – No
269 Plus – Yes
Yes Yes
Analog Output Yes Yes Yes
Communication Modbus Modbus DeviceNet, Modbus
Trip Contacts 1 form C 1 form C 1 form C
Alarm Contacts 1 form C 1 form C 1 form A or B
The 825 Plus core balance/ground fault current transformer (GFCT) input has an operating range of 5 to 500 mA. Care is required to ensure
this input range is not exceeded. When existing CT has a ratio of 50:0.025 (2000:1), the minimum trip level is 10A primary. For lower trip
levels, the core balance/GFCT will need to be replaced with a 100:1 ratio CT. Refer to the catalog number breakdown for part numbers of
various donut CT window sizes.