Installation Instructions
Bulletin 1494R Lug Adapter Kit Installation Instructions
(Cat 1494R-N16, 1494R-N17, 1494R-N18, 1494R-N19)
(For use with Bulletin 1494C, 1494F, 1494G, 1494V Disconnect Switches)
To prevent electrical shock, disconnect from power source before installing or servicing,
Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
Wire Clamp
Adapter
Wire Lug
Disconnect Switch
Lug Adapter Kit Line and Load Lugs
Adapter
Torque
(Lb.-In.)
Catalog
Number
Catalog
Number
Wire
Clamp
Torque
(Lb.-In.)
Wire Lug
Torque
(Lb.-In.)
Wire Clamp
Wire Range
Wire Lug
Wire Range
Disconnect
Switch
Rating (Size)
Notes:
* 1. Assemble Washer beneath adapter for 30 amp. (See view)
1494R-N16
Included with
Switch
#14-#8 Cu,
Solid or
Stranded
#14-#4 Cu,
Solid or
Stranded
#8-#1/0 Cu,
Solid or
Stranded
#6-#4/0 Cu,
Solid or
Stranded
30A 25-28
1494R-N17 1494R-N1
1494R-N2
1494R-N3
60A 40-60
25
20
45
150
275
(1) 14-10 STR/SOL
(1) 8 STR
(2) 14 SOL/SOL
(2) 14 STR/STR
(2) 12 SOL/SOL
(2) 12 STR/STR
(2) 10 SOL/SOL
(2) 10 STR/STR
(2) 8 STR/STR
1494R-N18 100A 90-110
1494R-N19 200A / 400A 175-200
See Note 1
PN-43715
DIR 10000050673 (Version 02)
Printed in U.S.A.
2
1
WARNING