Manual
Bulletin 1494F Disconnect Switch and Accessory Kits
4
Publication 1494F-IN014C-EN-E - January 2013 42052-105-01 DIR 42052-105 (Version 03)
Trailer Fuse Block Installation
Note: Not required for non-fusible disconnect switch applications.
1. Refer to the gures and chart below to determine the position on the mounting plate and the orientation of
the trailer fuse block.
400 Amp Disconnect Switch
and Trailer Fuse Block on a
NEMA Size 5 Combination Starter
Position
3
5
1
4
6
2
Amps
200
200
200
400
400
400
Voltage
250
600
600
250
600
600
Fuse Class
H/R
H/R
J
H/R
H/R
J
Position 1
Position 2
Position 3
Position 4
Position 5
Position 6
90 - 130 lb-in