Chapter 1
Installation
This chapter describes how to install a 1442 Series Eddy Current Probe System.
ATTENTION: Always ground the system. Never apply power until all
wiring work and connection work has been completed. If this is not
followed, there is a possibility of electrocution.
Installation work, wiring, and connections must be performed by a person
with knowledge in instrumentation.
ATTENTION: Be sure to adhere to the following guidelines:
Before touching this unit, be sure to touch a metal section near by to
discharge any static electricity. The device can be damaged if exposed to
static electricity from a persons body.
Before applying power, make sure that all wiring is properly connected.
There is a possibility of damage to the unit and fire if improperly
connected.
Install this unit away from motors and relays.
Install the input/output signal cables away from power system and
control system cables. Noise occurring from the motor or relay can
adversely affect the measurement value. We recommend using separate
wiring ducts.
Do not pull or bend the sensor cables and extension cables with
excessive force. The conductor in the cable can get cut off.
The allowable tension of the sensor cables and extension cables is
98.1 N•m (10 kgf•m). The allowable bend radius is as follows:
Without armored cable: 30 mm (1.18 in.)
With armored cable: 50 mm (1.97 in.)
After completing the installation, make sure all connections are correct
and tight before powering the system.
TIP
Refer to Appendix A on page 51 for recommended cable wiring, and
installation methods.