Owner's manual
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Objects 91
1 The Poll Connection Produced Connection Path and Size parameters cannot be set while the Poll connection is
already established with a master/scanner. Attempting to do so will result in an “Object State Conflict” error
(error code 0xC). These Parameter instances are a little more flexible than the actual Connection Object
attributes because they can be set while the connection is in the NON=EXISTENT state (before the master/
scanner allocated the connection).
5 No Eccentricity 1 Update Rate USINT 1-255 seconds 60
6 No Eccentricity 2 Update Rate USINT 1-255 seconds 60
7 No Relay 1 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
8 No Relay 2 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
9 No Relay 3 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
10 No Relay 4 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
11 No Relay 5 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
12 No Relay 1 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
13 No Relay 2 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
14 No Relay 3 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
15 No Relay 4 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
16 No Relay 5 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
17 No Poll Connection Produced
Connection Path
1
USINT 101-104 (Assembly Object
instance number)
101
18 No Poll Connection Produced
Connection Size
1
UINT 4 - 124 36
Table C.25 Parameter Object Instances
Instance
Read
Only Name Data Type Valid Values Default Value