Owner's manual
Publication GMSI10-UM010C-EN-P - May 2010
DeviceNet Objects 95
Services
The settable attributes of this object are not affected by the status of the
Device Mode Object.
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
11 Get/Set Danger Threshold
Low
(Counterclockwise)
REAL The lesser threshold value
for the danger (shutdown)
condition for the range
condition types.
12 Get/Set Hysteresis REAL The amount on the safe
side of a threshold by
which the value must
recover to clear the alarm.
15 Get/Set Speed Range
Enable
BOOL Indicates whether this
alarm is enabled only
within a certain machine
speed range.
0 = No speed range (alarm is
always enabled)
1 = Speed range (alarm enabled
only within speed range)
16 Get/Set Speed Range High REAL Indicates the greater
threshold of the machine
speed range for which the
alarm is enabled (disabled
at greater speeds).
CPM
(Must be greater than Speed
Range Low)
17 Get/Set Speed Range Low REAL Indicates the lesser
threshold of the machine
speed range for which the
alarm is enabled (disabled
at lesser speeds).
CPM
(Must be less than Speed
Range High)
18 Get/Set Name STRING2 A name to help identify
this alarm.
Table C.30 Alarm Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
Table C.31 Alarm Object Services
Service
Code Class/Instance Usage Name Description
0E
h
Instance Get_Attribute_Single Returns a single attribute.
10
h
Instance Set_Attribute_Single
Sets a single attribute.
1