Manual
Publication GMSI10-UM014D-EN-P - May 2010
DeviceNet Objects 113
1 This attribute is read-only for instance 1. The instance 1 setting is based upon the instance 2 setting. If the
Channel 2 Output Data Units are English, then the Channel 1 Output Data Units will be mils. If the Channel 2
Output Data Units are Metric, then the Channel 1 Output Data Units will be µm.
2 This attribute cannot be set for instance 2. The instance 2 setting matches the channel 1 setting.
10 Get/Set Full Scale REAL The maximum signal
expected to be processed
by the channel.
Volts peak
Setting the Full Scale to a
greater value allows the
channel to handle greater input
signals without saturating or
clipping. Setting the Full Scale
to a lesser value allows the
signal to be measured with
greater resolution.
100 Get Very Low HPF
Corner
Frequency
REAL The frequency, in Hz, of
the "Very low" Low
Cutoff Frequency option
for attribute 5.
Hz
101 Get Low HPF Corner
Frequency
REAL The frequency, in Hz, of
the "Low" Low Cutoff
Frequency option for
attribute 5.
Hz
102 Get Medium HPF
Corner
Frequency
REAL The frequency, in Hz, of
the "Medium" Low
Cutoff Frequency (low
frequency corner) option
for attribute 5.
Hz
103 Get High HPF Corner
Frequency
REAL The frequency, in Hz, of
the "High" Low Cutoff
Frequency option for
attribute 5.
Hz
104 Get Very High HPF
Corner
Frequency
REAL The frequency, in Hz, of
the "Very high" Low
Cutoff Frequency option
for attribute 5.
Hz
Table C.31 Channel Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics