Manual
Publication GMSI10-UM014D-EN-P - May 2010
DeviceNet Objects 111
Services
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Channel Object
(Class ID 31F
H
)
The Channel Object models "front-end" processing performed on an input
signal before specific measurements are performed. This processing typically
includes gain, filtering, and/or integration.
Class Attributes
The Channel Object provides no class attributes.
17 Get/Set Speed Range Low REAL Indicates the lesser
threshold of the machine
speed range for which the
alarm is enabled (disabled
at lesser speeds).
CPM
(Must be less than Speed
Range High)
18 Get/Set Name STRING2 A name to help identify
this alarm.
20 Get/Set Inhibit Tach Fault BOOL Determines whether the
Tach Fault status is
prohibited during the
startup period.
0 = Tach Fault allowed
1 = Tach Fault inhibited
Table C.28 Alarm Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
Table C.29 Alarm Object Services
Service
Code Class/Instance Usage Name Description
0E
h
Instance Get_Attribute_Single Returns a single attribute.
10
h
Instance Set_Attribute_Single
Sets a single attribute.
1