User guide

8 Rockwell Automation Publication GMSI10-IN026C-EN-P - February 2014
XM-160, XM-161, and XM-162 Direct Vibration Modules
Channel Status Indicator (six in all)
Self-Test
The XM-16X modules perform a self-test at powerup. The self-test includes a status indicator test and a device test. During
the status indicator test, the indicators are turned on independently and in sequence for approximately 0.25 seconds.
The device test occurs after the status indicator test. The Module Status (MS) indicator is used to indicate the status of the
device self-test.
Reset Switch
The XM-16X modules have an external reset switch on top of the module. The Reset switch can be used to reset all latched
relays in the Relay Expansion module when it is attached to an XM-16X module.
Color State Description
No color Off Normal operation with alarm limits on the channel.
No power applied to the module; look at Module Status indicator.
Yellow Solid An alert level alarm condition exists on the channel (and no transducer fault or danger level alarm condition exists).
Red Solid A danger level alarm condition exists on the channel (and no transducer fault condition exists).
Flashing A transducer fault condition exists on the channel.
MS Indicator State Description
Flashing red and green Device self-test is in progress.
Solid green or flashing green Device self-test completed successfully, and the firmware is valid and running.
Flashing red Device self-test completed, the hardware is OK, but the firmware is invalid.
The firmware download is in progress.
Solid red Unrecoverable fault, hardware failure, or Boot Loader program corruption.
IMPORTANT
The Reset switch resets the relays only if the input is no longer in alarm or the condition that caused the alarm is no longer
present.
Reset Switch