Owner's manual
Publication GMSI10-UM003D-EN-P - May 2010
58
Fault Low The minimum, or most negative, expected DC
voltage from the transducer.
Volts
Note: A voltage reading outside this
range constitutes a transducer fault.
Fault High The maximum expected DC voltage from the
transducer.
DC Bias Time Constant The time constant used for exponential averaging
(low pass filtering) of the transducer DC bias
measurement. The corner frequency for the low pass
filter is 1 / (2 x
π x DC Bias Time Constant). See
example table below.
Seconds
Tachometer Transducer Parameters
Parameter Name Description Values/Comments
Time Constant
(seconds)
-3dB Frequency
(Hz)
Settling
(seconds)
1 0.159 2.2
2 0.080 4.4
3 0.053 6.6
4 0.040 8.8
50.03211
60.02713.2
70.02315.4
80.02017.6
90.01819.8
10 0.016 22