Owner's manual

Publication GMSI10-UM003D-EN-P - May 2010
144
XM-123 Full Scale Tables
Use the following tables to help you determine the optimal Full Scale value for
the XM-123 module. Refer to the table that corresponds to the units of
vibration that will be used for monitoring.
Table D.1 XM-123 Measuring Acceleration with Accelerometer (100 mV/g)
Max Vibration Level Full Scale Setting
g’s peak 1Hz HPF 5Hz HPF 10Hz HPF 40Hz HPF 1000Hz HPF
10.1
50.75
10 1
30 3
40 4
50 5
Table D.2 XM-123 Measuring Velocity with Accelerometer (100 mV/g)
Max Vibration Level Full Scale Setting Max High Frequency Peak Amplitude
ips peak mm/s RMS 1Hz HPF 5Hz HPF 10Hz HPF 40Hz HPF 1000Hz HPF (g pk)
0.3 10
N/A
0.005 0.01 0.03 0.75 4
140
N/A
4
3 100 0.009 0.018 0.072 4
10 360 0.085 0.17 0.67 12
30 1000 0.25 0.5 2.2 40
100 3600 0.83 1.66 6.66 120
Table D.3 XM-123 Measuring Velocity with Velocimeter (100 mV/ips)
Max Vibration Level Full Scale Setting
ips peak mm/s RMS 1Hz HPF 5Hz HPF 10Hz HPF 40Hz HPF 1000Hz HPF
3 100 0.75
10 360 1
20 700 2
30 1000 3
Table D.4 XM-123 Measuring Displacement with Velocimeter (100 mV/ips)
Max Vibration Level Full Scale Setting
mils pp micrometers pp 1Hz HPF 5Hz HPF 10Hz HPF 40Hz HPF 1000Hz HPF
5 125
N/A
0.05 0.1 0.35
N/A
10 250 0.1 0.2 0.7
50 1250 0.15 0.3 1.05