Services
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
5 Get/Set Sensitivity
Value
REAL Value of the sensitivity of
the transducer in
millivolts per Sensitivity
Units.
6 Get/Set Sensitivity Units ENGUNIT Units of the denominator
of the Sensitivity Value.
See DeviceNet Specification
Volume 1 Appendix K.
Valid values:
g =1504 hex
in/sec = 2B07 hex
mils = 0800 hex
psi = 1300 hex
volt = 2D00 hex
mm/s = 0900 hex
µm = 2204 hex
Pa = 1309 hex
7 Get/Set Fault High REAL The maximum expected
DC Bias voltage from the
transducer in volts.
Volts
8 Get/Set Fault Low REAL The minimum expected
DC Bias voltage from the
transducer in volts.
Volts
9 Get/Set Power Type USINT Indicates the type of
power supplied to the
transducer.
0 = No power supplied
1 = Constant current (IEPE
accelerometer)
13 Get/Set DC Bias Time
Constant
REAL The time constant value
used for exponential
averaging of the DC Bias
value (a low pass
filter/output smoothing
filter).
Seconds
Table C.48 Transducer Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
Table C.49 Transducer Object Services
Service
Code Class/Instance Usage Name Description
0E
h
Instance Get_Attribute_Single Returns a single attribute.
10
h
Instance Set_Attribute_Single
Sets a single attribute.