Manual

Publication GMSI10-UM008D-EN-P - August 2010
76
The Poll response data can also be requested explicitly through Assembly
Object (Class ID 0x4), Instance 101 (0x65) – 103 (0x67), Data Attribute (3).
The following tables show the static data format of Assembly instance 101–
103.
XM-361/362 Assembly Instance 101 Data Format
Byte Definition
0–3 Channel 1 measurement value
4–7 Channel 2 measurement value
8-11 Channel 3 measurement value
12-15 Channel 4 measurement value
16-19 Channel 5 measurement value
20-23 Channel 6 measurement value
24-27 Channel 1 rate of change value
28-31 Channel 2 rate of change value
32-35 Channel 3 rate of change value
36-39 Channel 4 rate of change value
40-43 Channel 5 rate of change value
44-47 Channel 6 rate of change value
XM-361/362 Assembly Instance 102 Data Format
Byte Definition
0–3 Channel 1 rate of change value
4–7 Channel 2 rate of change value
8-11 Channel 3 rate of change value
12-15 Channel 4 rate of change value
16-19 Channel 5 rate of change value
20-23 Channel 6 rate of change value
24-27 Channel 1 measurement value
28-31 Channel 2 measurement value
32-35 Channel 3 measurement value
36-39 Channel 4 measurement value
40-43 Channel 5 measurement value
44-47 Channel 6 measurement value