Manual
Publication GMSI10-UM008D-EN-P - August 2010
99
1 The Poll Connection Produced Connection Path and Size parameters cannot be set while the Poll Connection is
already established with a master/scanner. Attempting to do so will result in an "Object State Conflict" error
(error code 0XC). These Parameter instances are a little more flexible than the actual Connection Object
attributed because they can be set while the connection is in the NON-EXISTENT state (before the
master/scanner allocates the connection).
Instance Attributes
26 Yes Channel 2 Difference REAL Channel 2 - Channel 1
27 Yes Channel 3 Difference REAL Channel 3 - Channel 2
28 Yes Channel 4 Difference REAL Channel 4 - Channel 3
29 Yes Channel 5 Difference REAL Channel 5 - Channel 4
30 Yes Channel 6 Difference REAL Channel 6 - Channel 5
31 No 4-20 mA Output 1
Measurement Identifier
USINT 0 = Measurement Value
1 = Difference Value
0
32 No 4-20 mA Output 2
Measurement Identifier
USINT 0 = Measurement Value
1 = Difference Value
0
33 No 4-20 mA Output 3
Measurement Identifier
USINT 0 = Measurement Value
1 = Difference Value
0
34 No 4-20 mA Output 4
Measurement Identifier
USINT 0 = Measurement Value
1 = Difference Value
0
35 No 4-20 mA Output 5
Measurement Identifier
USINT 0 = Measurement Value
1 = Difference Value
0
36 No 4-20 mA Output 6
Measurement Identifier
USINT 0 = Measurement Value
1 = Difference Value
0
37 No Enable Relay Reset Switch BOOL 0 = Disabled
1 = Enabled
0
38 No Sensor OOR Allowance REAL 0-5% 0.0
Table C.24 Parameter Object Instances
Instance
Read
Only Name Data Type Valid Values Default Value
Table C.25 Parameter Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
1 Set Parameter
Value
Actual value of parameter See Table C.24 for a list of valid
values for each instance.
2 Get Link Path Size USINT Size of Link Path 0 (These Parameter instances do
not link directly to another
object attribute.)