Instruction Manual
Publication GMSI10-UM005C-EN-P - May 2010
DeviceNet Objects 107
Instances
There are 2 instances of this object.
Instance Attributes
Services
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Table C.40 4-20mA Output Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
3 Get/Set Value REAL The current output value. mA
4 Get/Set Enable BOOL Indicates whether this
4-20mA output is
enabled.
0 = Disabled
1 = Enabled
5 Get/Set Max Range REAL The measured value
associated with 20mA.
6 Get/Set Min Range REAL The measured value
associated with 4mA.
Table C.41 4-20mA Output Object Services
Service
Code Class/Instance Usage Name Description
0E
h
Instance Get_Attribute_Single Returns a single attribute.
10
h
Instance Set_Attribute_Single
Sets a single attribute.
1