Instruction Manual
Publication GMSI10-UM005C-EN-P - May 2010
96 DeviceNet Objects
Instances
There are 15 instances of this object.
Table C.25 Parameter Object Instances
Instance
Read
Only Name Data Type Valid Values Default Value
1 No Transducer 1 Sensitivity Units USINT 0 = mils
1 = degrees of rotation
2 = mm
3 = percent
0
2 No Transducer 2 Sensitivity Units USINT 0 = mils
1 = degrees of rotation
2 = mm
3 = percent
0
3 No Position Measurement 1 Units USINT 0 = mils
1 = degrees of rotation
2 = mm
3 = percent
0
4 No Position Measurement 2 Units USINT 0 = mils
1 = degrees of rotation
2 = mm
3 = percent
0
5 No Mode USINT 0 = Normal
1 = Head-to-Head
2 = Radial Cancel
0
6 No Relay 1 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
7 No Relay 2 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
8 No Relay 3 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
9 No Relay 4 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
10 No Relay 5 Alarm Identifier A USINT 0 = Alarm 1
1 = Alarm 2
0
11 No Relay 1 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
12 No Relay 2 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
13 No Relay 3 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
14 No Relay 4 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0
15 No Relay 5 Alarm Identifier B USINT 0 = Alarm 1
1 = Alarm 2
0