Owner manual

Publication GMSI10-UM006C-EN-P - August 2010
DeviceNet Objects 85
Instance 101 - Measurement Values
This assembly instance can be selected to be sent in response to an I/O Poll
Request from a Master. This instance is the default Poll response selection.
Instance 102 - Measurement Values
This assembly instance can be selected to be sent in response to an I/O Poll
request from a Master.
Table C.11 Instance 101 Data Format (Measurement Values Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 - 3 Channel 1 Process (DC) Measurement value
4 - 7 Channel 2 Process (DC) Measurement value
8 - 11 Channel 3 Process (DC) Measurement value
12 - 15 Channel 4 Process (DC) Measurement value
16 - 19 Channel 5 Process (DC) Measurement value
20 - 23 Channel 6 Process (DC) Measurement value
24 - 27 Channel 1 Rate of Change value
28 - 31 Channel 2 Rate of Change value
32 - 35 Channel 3 Rate of Change value
36 - 39 Channel 4 Rate of Change value
40 - 43 Channel 5 Rate of Change value
44 - 47 Channel 6 Rate of Change value
48 - 51 Channel 1 - Channel 6 Difference
52 - 55 Channel 2 - Channel 1 Difference
56 - 59 Channel 3 - Channel 2 Difference
60 - 63 Channel 4 - Channel 3 Difference
64 - 67 Channel 5 - Channel 4 Difference
68 - 71 Channel 6 - Channel 5 Difference
Table C.12 Instance 102 Data Format (Measurement Values Assembly)
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 - 3 Channel 1 Rate of Change value
4 - 7 Channel 2 Rate of Change value
8 - 11 Channel 3 Rate of Change value
12 - 15 Channel 4 Rate of Change value
16 - 19 Channel 5 Rate of Change value
20 - 23 Channel 6 Rate of Change value
24 - 27 Channel 1 Process (DC) Measurement value