Owner manual

Publication GMSI10-UM006C-EN-P - August 2010
40 Installing the XM-360 Process Module
Module Status (MS) Indicator
1 Program Mode - Typically this occurs when the module configuration settings are being updated with the XM
Serial Configuration Utility. In Program Mode, the module does not perform its usual functions. The signal
processing/measurement process is stopped, and the status of the alarms is set to the disarm state to prevent
a false alert or danger status.
2 Run Mode - In Run Mode, the module collects measurement data and monitors each measurement device.
Network Status (NS) Indicator
1 Normal condition when the module is not a slave to an XM-440, PLC, or other master device.
Color State Description
No color Off No power applied to the module.
Green Flashing Red Module performing power-up self test.
Flashing
Module operating in Program Mode
1
.
Solid
Module operating in Run Mode
2
.
Red Flashing Application firmware is invalid or not loaded.
Download firmware to the module.
Firmware download is currently in progress.
The module power voltage is incorrect.
Solid An unrecoverable fault has occurred. The module may
need to be repaired or replaced.
Color State Description
No color Off Module is not online.
Module is autobauding.
No power is applied to the module, look at Module
Status LED.
Green Flashing Module is online (DeviceNet) but no connections are
currently established.
1
Solid Module is online with connections currently
established.
Red Flashing One or more I/O connections are in the timed-out state.
Solid Failed communications (duplicate MAC ID or bus-off).