Instruction Manual

Rockwell Automation Publication ENMON-IN220D-EN-P - February 2014 7
XM-220 Dual Speed Module
Module Indicators
The XM-220 module has seven status indicators, which are on top of the module.
Module Status (MS) Indicator
Network Status (NS) Indicator
1
TIP
The AUX indicator is reserved for future use.
Color State Description
No color Off No power applied to the module.
Green Flashing red Module performing power-up self-test.
Flashing Module operating in Program mode.
(1)
(1) Program mode - Typically this occurs when the module configuration settings are being updated with the XM Serial Configuration Utility. In Program mode, the module does not perform its normal
functions. The signal processing/measurement process is stopped, and the status of the alarms is set to the disarm state to prevent a false alert or danger status.
Solid Module operating in Run mode.
(2)
(2) Run mode - In Run mode, the module collects measurement data and monitors each measurement device.
Red Flashing Application firmware is invalid or not loaded. Download firmware to the module.
Firmware download is currently in progress.
Solid An unrecoverable fault has occurred. It is possible that the module must be repaired or replaced.
Color State Description
No color Off Module is not online:
Module is autobauding.
No power applied to the module; look at Module Status indicator.
Green Flashing Module is online (DeviceNet network) but no connections are currently established.
(1)
(1) Normal operation when the module is not a slave to an XM-220, programmable controller, or other master device.
Solid Module is online with connections currently established.
Red Flashing One or more I/O connections are in the timed-out-state.
Solid Failed communication (duplicate MAC ID or bus-off).