Specifications
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication
1770-4.1.
XM ControlNet Adapter - 1440-ACNR
Attribute Value
Enclosure Type Rating None (open-style)
Input Voltage 24V DC
Current Draw Max 120 mA
XM Bus Output 24V DC, 3 A Max
Isolation Voltage 50V (continuous), Basic Insulation Type
Type tested at 900V AC for 60 s, between
ControlNet to system and ControlNet to
power.
Wire Size Power connections:
0.34... 2.1 mm
2
(22...14 AWG) solid or
stranded copper wire rated at 75 °C (167
°F ) or greater 1.2 mm (3/64 in.) insulation
max
Wiring Category
(1)
1 - on power ports
2 - on communications ports
North American Temp Code T4A
IEC Temp Code T4
Environmental Specifications
Attribute Value
Operating Temperature
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal
Shock):