Owner's manual

XM ControlNet Adapter 11
Publication
ICM-IN001A-EN-P - March 2009
2. Connect the redundant ControlNet network cable to connector B.
3. Connect +V DC power to the lower connector, terminal F or D.
4. Connect -V common to the upper connector, terminal E or C.
Set the Node Address
Set the network address using the 2-button pushwheel switch (G). Valid
settings range from 01 to 99.
ATTENTION
When connecting wiring, torque terminal screws C, D, E, and F to 0.8 Nm
(7
lb-in).
2
5
Press either the + or
- buttons to change
the number.
Network
Address
Switches