Owner's manual

XM ControlNet Adapter 13
Publication
ICM-IN001B-EN-P - March 2013
1. Connect the ControlNet network cable to connector A.
2. Connect the redundant ControlNet network cable to connector B.
3. Connect +V DC power to the lower connector, terminal F or D.
4. Connect -V common to the upper connector, terminal E or C.
WARNING
The NAP port is intended for temporary local programming purposes only and
not intended for permanent connection. If you connect or disconnect the NAP
cable with power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
ATTENTION
When connecting wiring, torque terminal screws C, D, E, and F to 0.8 N•m
(7 lb•in.).
ControlNet XM Adapter
2
5
1440-ACNR
AB
A
BG
CE
DF