Chapter 5 Power Quality Monitoring
These bitfields reports the short-term or long-term status of harmonics of order
18
33.
0 = PASS
1 = FAIL
Bit0 - 18th_Harmonic_PASS_FAIL
Bit1 - 19th_Harmonic_PASS_FAIL
Bit15 - 33rd_Harmonic_PASS_FAIL
ShortTerm_34th_To_40th_Harmonic_Status
LongTerm_34th_To_40th_Harmonic_Status
These bitfields reports the short-term or long-term status of harmonics of order
34 through 40.
0 = PASS
1 = FAIL
Bit0 - 34th_Harmonic_PASS_FAIL
Bit1 - 35th_Harmonic_PASS_FAIL
Bit6 - 40th_Harmonic_PASS_FAIL
Bit 7 … Bit 15 - Reserved, always = 0
IEEE-519 Short Term and
Long Term Harmonic Results
The six data tables listed below provide an indication of individual current
harmonic distortion and TDD (Total Demand Distortion). If the user has
selected voltage as the output parameter the tables list voltage distortions and
THD (Total Harmonic Distortion).
PowerQuality.IEEE519_CH1_ShortTerm_Results
PowerQuality.IEEE519_CH2_ShortTerm_Results
PowerQuality.IEEE519_CH3_ShortTerm_Results
PowerQuality.IEEE519_CH1_LongTerm_Results
PowerQuality.IEEE519_CH2_LongTerm_Results
PowerQuality.IEEE519_CH3_LongTerm_Results
Each table provides the following:
Timestamp of the most recent results
Fundamental magnitude
Individual harmonic distortion as a percentage of the fundamental
magnitude
Overall distortion
With current selected as the compliance parameter (default), if the
IEEE519_MAX_Isc and IEEE519_MAX_IL parameter values are
non-zero, then TDD is returned. Otherwise, THD is returned.