Chapter 5 Power Quality Monitoring
Waveform Distortion
(Category 5.1 - DC Offset, and
5.2 - Harmonics) (M6 model)
The PowerMonitor 5000 M6 model detects and reports long-term waveform
distortion in excess of configured limits. Categories 5.3, 5.4 and 5.5 are not
supported in the M6 model.
Setup
Basic metering setup required. These configuration parameters are found in the
Configuration.PowerQuality tab:
IEEE1159_DCOffsetAndHarmonics_Averaging_Intvl_m - rolling
average interval for DC offset and harmonics, range = 1
15 minutes,
default = 5 minutes
IEEE1159_Voltage_DCOffset_Limit_% - DC offset alarm threshold,
range = 0.00
1.00 per cent of fundamental, default = 0.1 per cent
IEEE1159_Voltage_THD_Limit_% - voltage THD alarm threshold,
range = 0.00
20.00 per cent of fundamental, default = 5 per cent
IEEE1159_Current_THD_Limit_% -current THD alarm threshold,
range = 0.00
20.00 per cent of fundamental, default = 10 per cent
Operation
The M6 model measures voltage and current THD, over the specified rolling
average interval and annunciates if these THD values exceed the specified
thresholds. The rolling average is updated at a rate of 10 seconds per minute of
the specified interval.
The PowerMonitor 5000 unit does not measure current DC offset because the
CTs do not pass DC. DC offset is measured on directly-connected voltage
channels and is tracked in the power quality log.
Status
These status bits annunciate over limit conditions and remain asserted until the
parameter is no longer over the threshold. A value of 1 indicates over limit. They
are found in the Status.Alarms tab.
IEEE1159_DCOffset_Condition_V1
IEEE1159_DCOffset_Condition_V2
IEEE1159_DCOffset_Condition_V3
IEEE1159_Voltage_THD_Condition_V1
IEEE1159_Voltage_THD_Condition_V2
IEEE1159_Voltage_THD_Condition_V3
IEEE1159_Current_THD_Condition_ I1
IEEE1159_Current_THD_Condition_ I2
IEEE1159_Current_THD_Condition_ I3