Chapter 4 Metering
Metering Overview
The PowerMonitor 5000 unit performs calculations on scaled, digital voltage,
and current values. Signals connected to the voltage and current inputs are
sampled and their instantaneous values are converted to digital values in an
analog-to-digital (A/D) converter section. These values are scaled according to
configured PT Primary, PT Secondary, CT Primary, and CT Secondary
parameters, and evaluated according to the configured Wiring Mode parameter.
All metering results can be viewed by using the Web interface,
FactoryTalk EnergyMetrix software, version 2.0, or standard CIP
communication.
Summary of Measurements
Current: Average Current, Positive/Negative/Zero Sequence, Percent
Unbalance
Voltage: Line-Line, Line-Neutral, Average, Positive/Negative/Zero
Sequence, Percent Unbalance
Frequency, Average Frequency
Power: Real (W), Reactive (VARs), Apparent (VA), Total
Power Factor: True (Full Bandwidth), Displacement (Fundamental ),
Lead, Lag, Demand
Real Energy Consumption (kWh, GWH), Forward, Reverse, Net
Reactive Energy Consumption (kVARh, GVARh) Forward, Reverse, Net
Apparent Energy Consumption (kVAh, GVAh) Net
Current Consumption (Amp-h)
Demand and Projected Demand (kA, kW, kVAR, kVA)
IEEE Percent Total Harmonic Distortion
IEC Percent Total Harmonic Distortion
Crest Factor
K-Factor
Phase Rotation (ABC, ACB)
Time of Use
Metering Accuracy Class
ANSI C12.20 -2010 (clause 8) Class 0.2 and
EN 62053-22 - 2003 (clause 5.5.4) Class 0.2