Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 41
Chapter 3
Setup
Although the PowerMonitor 5000 unit ships from the factory with default
settings, you need to configure it for your particular requirements. The
PowerMonitor 5000 unit provides a built-in Web interface for monitoring and
configuration through its native Ethernet communication port and its USB
device port. You perform initial configuration by using the power monitor's built-
in USB Web interface. Once initial setup is complete, you can continue
configuring the PowerMonitor 5000 unit by using its USB or network Web
interface, by using optional software, or by communicating with the power
monitor's data table.
This section describes how to use the USB and Ethernet Web interface for setup.
You can find information on configuring various functions of the
PowerMonitor 5000 unit in the following chapters:
• Chapter 4
, Metering.
• Chapter 5
Power Quality Monitoring
• Chapter 6 Logging
• Chapter 7 Logic Functions
• Chapter 8 Other Functions
If you are using optional software, such as FactoryTalk EnergyMetrix software,
please refer to publication
FTALK-UM001,
for information. If you are using data communication for setup,
refer to the Communication
on page 181 for information.
Setup Using the Web
Interface
For initial setup, connect a personal computer to the PowerMonitor 5000 unit by
using a USB cable. Refer to USB Communication
on page 31.
Initial setup is usually performed by using the USB Web interface and initial
security setup can be performed only by using the USB Web interface.