Appendix A PowerMonitor 5000 Unit Data Tables
For example, the tag I1_Amps_h5_H_RMS in the
PowerQuality.I1_Amps_H1_RMS (DC…31) table returns the RMS magnitude
of the 5th harmonic for Line 1 current.
Table 188 - Substitution Table
For: Substitute: To return these harmonic results:
<CH> Total Total (3-phase) power
L1 Line (Phase) 1 power
L2 Line (Phase) 2 power
L3 Line (Phase) 3 power
V1_N Line 1 to Neutral voltage
V2_N Line 2 to Neutral voltage
V3_N Line 3 to Neutral voltage
VN_G Neutral to Ground voltage
V1_V2 Line 1 to Line 2 voltage
V2_V3 Line 2 to Line 3 voltage
V3_V1 Line 3 to Line 1 voltage
I1 Line 1 current
I2 Line 2 current
I3 Line 3 current
I4 Line 4 current
<Units> kW Real power
kVAR Reactive power
kVA Apparent power
Volts Voltage
Amps Current
<Mag/Angle> RMS RMS magnitude
Ang Angle referenced to the metering time
stamp