Manual
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 351
PowerMonitor 5000 Unit Data Tables Appendix A
LoggingResults.Waveform_Log (M6 model)
Table 175 - Table Properties
CIP Instance Number 871
PCCC File Number F80
No. of Elements 43
Length in Words 86
Data Type Real
Data Access Read Only
Table 176 - LoggingResults. Waveform_Log Data Table
Element
Number
Type Tag Name Description Unit Range
0 Real Record_Indicator Indicates the significance of the data in the record 0 = No record returned
1= the record contains
parameter values
2 = the record contains
general information of
the log file being
retrieved, reference to
each item description in
the data table
3 = log file not found.
1 Real Timestamp_Date Date of cycle collection MMDDYY MMDDYY 0…123199
2 Real Timestamp_Time Time of cycle collection hhmmss hhmmss 0…235959
3 Real Microsecond_Stamp Microsecond of cycle collection uS 0.000…999999
4 Real File_ID The selected file ID # 1…256
5 Real Total_Cycles Total cycles of the waveform file # 0…3640
6 Real Cycle_Returned The current returned cycle # 0…(Total cycles - 1)
7 Real Frequency The frequency of average cycle Hz 40.0 … 75.0
8 Real Mag_Angle The returned value is mag or angle # 0 = Mag, 1 = Angle
9 Real Channel The channel returned # 0 = V1
1 = V2
2 = V3
3 = V4
4 = I1
5 = I2
6 = I3
7 = I4
10 Real Order The range of harmonic orders of returned values # 0 = DC…31st (M6)
1 = 32nd…63rd (M6)