Manual

348 Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A PowerMonitor 5000 Unit Data Tables
LoggingResults.TriggerData_Log (M6 model)
Table 167 - Table Properties
CIP Instance Number 861
PCCC File Number F70
No. of Elements 14
Length in Words 28
Data Type Real
Data Access Read Only
Table 168 - LoggingResults. TriggerData_Log Data Table
Element
Number
Type Tag Name Description Unit Range
0 Real Record_Indicator Indicates the significance of data in the record 0 = No record returned
1 = the record contains
parameter values
2 = the record contains general
information of the log file being
retrieved, reference to each item
description in the data table
3 = log file not found
1 Real TriggerData_Record_
Identifier
Internal unique record number, if Record_Indicator = 1
Total records number in the log file, if Record_Indicator = 2.
# 0 … 3600
2 Real TriggerData_
Timestamp_Year
The year when the record was recorded if Record_Indicator = 1. YYYY 2010…2100
3 Real TriggerData_
Timestamp_Month_D
ay
The month and day when the record was recorded Record_Indicator = 1. MMDD 0110…1231
4 Real TriggerData_
Timestamp_Hour_
Minute
The hour and minute when the record was recorded Record_Indicator = 1. hhmm 0000…2359
5 Real TriggerData_
Timestamp Sec_mS
The seconds and milliseconds when the record was recorded Record_Indicator = 1. ssmS 00000…59999
6 Real TriggerDataLog_P
arameter_1
Parameter value if Record_Indicator = 1
Parameter index (reference to Trigger Data Log Parameter List table) if
Record_Indicator = 2;
# +/- 0…9.999E15
7 Real TriggerDataLog_
Parameter_2
# +/- 0…9.999E15
8 Real TriggerDataLog_
Parameter_3
# +/- 0…9.999E15
9 Real TriggerDataLog_
Parameter_4
# +/- 0…9.999E15
10 Real TriggerDataLog_
Parameter_5
# +/- 0…9.999E15
11 Real TriggerDataLog_
Parameter_6
# +/- 0…9.999E15
12 Real TriggerDataLog_
Parameter_7
# +/- 0…9.999E15
13 Real TriggerDataLog_
Parameter_8
# +/- 0…9.999E15