Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 343
PowerMonitor 5000 Unit Data Tables Appendix A
LoggingResults.Setpoint_Log
Table 157 - Table Properties
CIP Instance Number 858
PCCC File Number F67
No. of Elements 18
Length in Words 36
Data Type Real
Data Access Read Only
Table 158 - LoggingResults.Setpoint_Log Data Table
Element
Number
Type Tag Name Description Unit Range
0 Real Setpoint_Record_Identifier Used to verify record sequence when returning multiple records. 1…100
1 Real Setpoint_Timestamp_Year The year when the record was recorded. YYYY 2010…2100
2 Real Setpoint_Timestamp_Mth_Day The month and day when the record was recorded. MMDD 11…1231
3 Real Setpoint_Timestamp_Hr_Min The hour and minute when the record was recorded. HHMM 0…2359
4 Real Setpoint_Timestamp_Sec_ms The seconds and milliseconds when the record was recorded. SSms 0…59,999
5 Real Setpoint_Number Setpoint number of record. 0…20
6 Real Setpoint_Status Setpoint is active (1) or not active (0). 0…1
7 Real Input_Parameter Input test parameter of setpoint. 0…105
8 Real Test_Condition Test Condition. 0…3
9 Real Evaluation_Type Evaluation type for setpoint. 1…3
10 Real Threshold_Setting The threshold setting magnitude or percent. 0.000…
10,000,000
11 Real Hysteresis_Setting Magnitude or percent 0.000…
10,000,000
12 Real Assert_Delay Time delay before actuation. seconds 0.000…3600
13 Real Deassert_Delay Time delay before deassert. seconds 0.000…3600
14 Real Output_Source Output flag or bit. 0…40
15 Real Output_Action Configured action when actuated. 0…TBD
16 Real Accumulated_Time Total accumulation in seconds. seconds 0.000
10,000,000
17 Real Number_Of_Transitions Number of transitions from off to on. 0…10,000,000