Manual
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 341
PowerMonitor 5000 Unit Data Tables Appendix A
LoggingResults.Alarm_Log
Table 153 - Table Properties
CIP Instance Number 856
PCCC File Number N65
No. of Elements 7
Length in Words 7
Data Type Int16
Data Access Read Only
Table 154 - LoggingResults.Alarm_Log Data Table
Element
Number
Type Tag Name Description Unit Range
0 Int16 Alarm_Record_Identifier Used to verify record sequence when returning multiple records. 1…100
1 Int16 Alarm_Timestamp_Year The year when the record was recorded. YYYY 2010…2100
2 Int16 Alarm_Timestamp_Mth_Day The month and day when the record was recorded. MMDD 11…1231
3 Int16 Alarm_Timestamp_Hr_Min The hour and minute when the record was recorded. HHMM 0…2359
4 Int16 Alarm_Timestamp_Sec_ms The seconds and milliseconds when the record was recorded. SSms 0…59,999
5 Int16 Alarm Type Indicates the type of event that has occurred. 0…512
6 Int16 Alarm Code Indicates information about the alarm. 0…4096