340 Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A PowerMonitor 5000 Unit Data Tables
LoggingResults.MIN_MAX.Log
28 Real On_Peak_kVAh_Net Net On Peak kiloVA hours kVAh 0…999,999
29 Real On_Peak_kVA_Demand On Peak Demand for kiloVA kVA 0.000…9,999,999
30…37 Real Resvd Reserved 0
Table 150 - LoggingResults.TOU.Log Data Table
Element
Number
Type Tag Name Description Units Range
Table 151 - Table Properties
CIP Instance Number 855
PCCC File Number F64
No. of Elements 11
Length in Words 22
Data Type Real
Data Access Read Only
Table 152 - LoggingResults.MIN_MAX.Log Data Table
Element
Number
Type Tag Name Description Units Range
0 Real MinMax_Parameter_Number The number of the parameter from the MIN_MAX parameter list. 1…82
1 Real MIN_Value The minimum value recorded since the last MIN_MIX clear. 9.999E-15…9.999E15
2 Real MAX_Value The maximum value recorded since the last MIN_MIX clear. 9.999E-15…9.999E15
3 Real Timestamp_MIN_Year The year at which this MIN record was logged. YYYY 0…9999
4 Real Timestamp_MIN_Mth_Day The month and day this MIN record was logged. MMDD 0…1231
5 Real Timestamp_MIN_Hr_Min The hour and minute this MIN record was logged. hhmm 0…2359
6 Real Timestamp_MIN_Sec_ms The seconds and milliseconds this MIN record was logged. SSms 0…59,999
7 Real Timestamp_MAX_Year The year at which this MAX record was logged. YYYY 0…9999
8 Real Timestamp_MAX_Mth_Day The month and day this MAX record was logged. MMDD 0…1231
9 Real Timestamp_MAX_Hr_Min The hour and minute this MAX record was logged. hhmm 0…2359
10 Real Timestamp_MIN_Sec_ms The seconds and milliseconds this MAX record was logged. SSms 0…59,999