Manual

336 Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A PowerMonitor 5000 Unit Data Tables
LoggingResults.Energy_Log
Table 145 - Table Properties
CIP Instance Number 852
PCCC File Number F61
No. of Elements 35
Length in Words 70
Data Type Real
Data Access Read Only
Table 146 - LoggingResults.Energy_Log Data Table
Element
Number
Type Tag Name Description Unit Range
0 Real Record_Indicator Indicate meanings of the data in the record 0 = No record returned
1 = the record contains
parameter values
2 = reserved
3 =l og file not found.
1 Real Energy_ Record_Identifier. Internal unique record number # ±0…9.999E15
2 Real Energy_Timestamp_Year The date and time when the record was recorded YYYY 2010 t…2100
3 Real Energy_Timestamp_Mth_Day MMDD 0110…1231
4 Real Energy_Timestamp_Hr_Min HHMM 0000…2359
5 Real Energy_Timestamp Sec_ms SSms 00000…59999
6 Real Status 1 Count xM Status 1 Count xM 0…9,999,999
7 Real Status 1 Count x1 x1 0…999,999
8 Real Status 2 Count xM Status 2 Count xM 0…9,999,999
9 Real Status 2 Count x1 x1 0…999,999
10 Real Status 3 Count xM Status 3 Count xM 0…9,999,999
11 Real Status 3 Count x1 x1 0…999,999
12 Real Status 4 Count xM Status 4 Count xM 0…9,999,999
13 Real Status 4 Count x1 x1 0…999,999
14 Real GWh Fwd Forward gigawatt hours GWh 0…9,999,999
15 Real kWh Fwd Forward kilowatt hours kWh 0.000…999,999
16 Real GWh Rev. Reverse gigawatt hours GWh 0…9,999,999
17 Real kwh Rev. Reverse kilowatt hours kWh 0.000…999,999
18 Real GWh Net Net gigawatt hours GWh ±0…9,999,999
19 Real kWh Net Net kilowatt hours kWh ±0.000…999,999
20 Real GVARH Fwd Forward gigaVAR hours GVARh 0…9,999,999
21 Real kVARh Fwd Forward kiloVAR hours kVARh 0.000…999.999
22 Real GVARH Rev. Reverse gigaVAR hours GVARh 0…9,999,999
23 Real kVARh Rev. Reverse kiloVAR hours kVARh 0.000…999.1000
24 Real GVARH Net Net gigaVAR hours GVARh ±0…9,999,999
25 Real kVARh Net Net kiloVAR hours kVARh ±0.000…999,999