Manual
334 Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A PowerMonitor 5000 Unit Data Tables
LoggingResults.Data_Log
Table 143 - Table Properties
CIP Instance Number 851
PCCC File Number F60
No. of Elements 38
Length in Words 76
Data Type Real
Data Access Read Only
Table 144 - LoggingResults.Data_Log Data Table
Element
Number
Type Tag Name Description Unit Range
0 Real Record_Indicator Indicates the meaning of the data in the record 0 = No record returned
1 = the record contains
parameter values
2 = the record contains
a reference to the item
description
3 = log file not found.
1 Real Data_Record_Identifier If Record_Indicator =1, internal unique record number
If Record_Indicator =2, total records number in the log file
# ±0…9.999E15
2 Real Data_Timestamp_Year If Record_Indicator =1, the date and time when the record was
recorded
otherwise 0
YYYY 2010…2100
3 Real Data_Timestamp_Month_Day MMDD 0110…1231
4 Real Data_Timestamp_Hour_Minute HHMM 0000…2359
5 Real Data_Timestamp Sec_ms SSms 00000…59999
6 Real DataLog_Parameter_1 If Record_Indicator =1, parameter value
If Record_Indicator =2 = parameter index: reference to Data Log
Parameter List table
(1)
±0…9.999E15
7 Real DataLog_Parameter_2 ±0…9.999E15
8 Real DataLog_Parameter_3 ±0…9.999E15
9 Real DataLog_Parameter_4 ±0…9.999E15
10 Real DataLog_Parameter_5 ±0…9.999E15
11 Real DataLog_Parameter_6 ±0…9.999E15
12 Real DataLog_Parameter_7 ±0…9.999E15
13 Real DataLog_Parameter_8 ±0…9.999E15
14 Real DataLog_Parameter_9 ±0…9.999E15
15 Real DataLog_Parameter_10 ±0…9.999E15
16 Real DataLog_Parameter_11 ±0…9.999E15
17 Real DataLog_Parameter_12 ±0…9.999E15
18 Real DataLog_Parameter_13 ±0…9.999E15
19 Real DataLog_Parameter_14 ±0…9.999E15
20 Real DataLog_Parameter_15 ±0…9.999E15
21 Real DataLog_Parameter_16 ±0…9.999E15
22 Real DataLog_Parameter_17 ±0…9.999E15
23 Real DataLog_Parameter_18 ±0…9.999E15