Appendix A PowerMonitor 5000 Unit Data Tables
29 Real L3_kVA L3 apparent power kVA 0…9.999E15
30 Real Total_kVA Total apparent power kVA 0…9.999E15
31 Real L1_True_PF_% L1 true power factor (full bandwidth) % 0.00…100.00
32 Real L2_True_PF_% L2 true power factor (full bandwidth) % 0.00…100.00
33 Real L3_True_PF_% L3 true power factor (full bandwidth) % 0.00…100.00
34 Real Avg_True_PF Average true power factor % 0.00…100.00
35 Real L1_Disp_PF L1 displacement power factor (fundamental only) % 0.00…100.00
36 Real L2_Disp_PF L2 displacement power factor (fundamental only) % 0.00…100.00
37 Real L3_Disp_PF L3 displacement power factor (fundamental only) % 0.00…100.00
38 Real Avg_Disp_PF Average displacement power factor (fundamental only) % 0.00…100.00
39 Real L1_PF_Lead_Lag_Indicator L1 lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
40 Real L2_PF_Lead_Lag_Indicator L1 lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
41 Real L3_PF_Lead_Lag_Indicator L1 lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
42 Real Total_PF_Lead_Lag_Indicator L1 lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
43 Real Voltage Rotation Voltage rotation has the following designations:
0 = Not metering
123 = ABC rotation
132 = ACB rotation
4 = No rotation
0…132
44 Real Metering_Iteration A number 0…9999999 that indicates that the metering
functions and internal communication are updating
0…9,999,999
45…55 Real Resvd Reserved
Table 136 - MeteringResults.RealTime_VIF_Power Data Table
Element
Number
Type Tag Name Description Units Range