Appendix A PowerMonitor 5000 Unit Data Tables
19 Int16 MeanPathDelayToMaster_A MeanPathDelayToMaster specifies the average path delay between the local clock and master clock
in nanoseconds. (Bit 0 to bit 15)
0…0xffff
20 Int16 MeanPathDelayToMaster_B MeanPathDelayToMaster specifies the average path delay between the local clock and master clock
in nanoseconds. (Bit 16 to bit 31)
0…0xffff
21 Int16 MeanPathDelayToMaster_C MeanPathDelayToMaster specifies the average path delay between the local clock and master clock
in nanoseconds. (Bit 32 to bit 47)
0…0xffff
22 Int16 MeanPathDelayToMaster_D MeanPathDelayToMaster specifies the average path delay between the local clock and master clock
in nanoseconds. (Bit 48 to bit 63)
0…0xffff
23 Int16 MasterClockIdentity_AB MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Master Clock. 0…0xffff
24 Int16 MasterClockIdentity_CD MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Master Clock. 0…0xffff
25 Int16 MasterClockIdentity_EF MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Master Clock. 0…0xffff
26 Int16 LocalClockIdentity_AB MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Local Clock. 0…0xffff
27 Int16 LocalClockIdentity_CD MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Local Clock. 0…0xffff
28 Int16 LocalClockIdentity_EF MAC address 0xA:0xB:0xC:0xD:0xE:0xF for the Local Clock. 0…0xffff
29 Int16 LocalClockClass An attribute defining a clock's TAI traceability 0…255
30 Int16 LocalTimeAccuracy An attribute defining the accuracy of a clock 0…255
31 Int16 LocalOffsetScaledLogVariance An attribute defining the stability of a clock 0…0xffff
32 Int16 NumberOfPorts NumberOfPorts specifies the number of PTP ports on the device. 1
33 Int16 PortState PortStateInfo specifies the current state of each PTP port on the device 1…9
34 Int16 DomainNumber DomainNumber specifies the PTP clock domain. 0…255
35 Int16 ClockType The value of ClockType shall indicate the type of PTP node as defined in Table 5-47.13 in CIP
sepecification Volume 1.
0…0xffff
36 Int16 Steps removed StepsRemoved specifies the number of communication paths traversed between the local clock and
the grandmaster clock.
0…0xffff
37…48 Int16 Reserved For future use
Table 122 - Status.IEEE1588 Data Table (M6 model)
Element
Number
Type Tag Name Description Range