Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 309
PowerMonitor 5000 Unit Data Tables Appendix A
Status.OptionalComm
Table 117 - Table Properties
CIP Instance Number 835
PCCC File Number N44
No. of Elements 30
Length in Words 30
Data Type Int16
Data Access Read Only
Table 118 - Status.OptionalComm Data Table
Element
Number
Type Tag Name Description Units Range
0 Int16 Network_Type 0x25 = DeviceNet
0x65 = ControlNet
-0255
1 Int16 Firmware_Version Optional communication firmware version Network_
Typ e
dependent
0…255
2 Int16 Firmware_Build Optional communication firmware build Network_
Typ e
dependent
0
3 Int16 Serial_Number_Low Low 16-bit serial number - 0
4 Int16 Serial_Number_High High 16-bit serial number - 0
5 Int16 Optional_Port_Status Bit15: Watchdog Timeout indicator
0: The application and ABCC communicate normally
1: The application lost the communication with ABCC module, so the watch dog times-out.
Bit14 to Bit5 reserved for future use.
Bit4: SUP bit
0: Module is not supervised;
1: Module is supervised.
Bit3 … Bit 0: Current status of Anybus module
000: SETUP
001: NW_INIT
010: WAIT_PROCESS
011: IDLE
100: PROCESS_ACTIVE
101: ERROR
110: reserved
111: EXCEPTION
-07
6 Int16 Exception_Code Last exception
0 = No exception
1 = Application timeout
2 = Invalid device address
3 = Invalid communication setting
4 = Major unrecoverable app event
5 = wait for reset
6 = Invalid process data config
7 = Invalid application response
8 = Non-volatile memory checksum error
Other value = reserved
-08