Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 289
PowerMonitor 5000 Unit Data Tables Appendix A
Configuration.WaveformFileName (M6 model)
Security.Username
Table 95 - Table Properties
CIP Instance Number 870
PCCC File Number ST79
No. of Elements 1
Length in Words 32
Data Type String
Data Access Write Only
Table 96 - Configuration.WaveformFileName Data Table
Element
Number
Type Tag Name Description Default Range
0 String Waveform_File_
Name
A single entry table for a 64 character Filename entry
‘Waveform_ID_YYYYMMDD_HHMMSS_MicroS_hh/cycle/ magorang/channel/iorder’
Where, YYYYMMDD_HHMMS is local date_time; hh is GMT hour;
cycle = current cycle offset returned (range is from 0 to total cycles - 1 in the waveform)
magorang = 0 is mag and 1 is angle
channel = the current channel returned (range is from 0 to 7)
iorder = 0 is DC to 31st, 1 is 32nd to 63rd, 2 is 64th to 95th and 3 is 96th to 127th
if only the file name is written, the retrieval is returned from the start of waveform;
0 64 bytes
Table 97 - Table Properties
CIP Instance Number 820
PCCC File Number ST29
No. of Elements 1
Length in Words 16
Data Type String
Data Access Write Only
Table 98 - Security.Username Data Table
Element
Number
Size Type Tag Name Description Default Range
0 32 String Username A single entry
table for a 32
character
Username entry
0 32 bytes