288 Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A PowerMonitor 5000 Unit Data Tables
Configuration.Harmonics_Optional_Read
Table 93 - Table Properties
CIP Instance Number 819
PCCC File Number N28
No. of Elements 15
Length in Words 15
Data Type Int16
Data Access Write
Table 94 - Configuration.Harmonics_Optional_Read Data Table
Element Number Type Tag Name Description Default Range
0 Int16 Channel Selection Selects the channel associated with the data returned in a
subsequent read of Table PowerQuality.Harmonics_Results.
0 = No Selection 1 = V1-N RMS,
2 = V2-N RMS 3 = V3-N,
4 = VN-G RMS 5 = V1-V2 RMS,
6 = V2-V3 RMS 7 = V3-V1 RMS
8 = I1 RMS 9 = I2 RMS
10 = I3 RMS 11 = I4 RMS
12 = L1 kW RMS 13 = L2 kW RMS
14 = L3 kW RMS 15 = L1 kVAR RMS
16 = L2 kVAR RMS 17 = L3 kVAR RMS
18 = L1 kVA RMS 19 = L2 kVA RMS
20 = L3 kVA RMS 21 = Total kW RMS
22 = Total kVAR RMS 23 = Total kVA RMS
24 = V1-N Angle 25 = V2-N Angle
26 = V3-N Angle 27 = VN-G Angle
28 = V1-V2 Angle 29 = V2-V3 Angle
30 = V3-V1 Angle 31 = I1 Angle
32 = I2 Angle 33 = I3 Angle
34 = I4 Angle
0 0…34
1 Int16 Harmonics Order
Range Selection
Selects harmonics order range. 1 = DC to 31st, 2 = 32nd to 63rd. 1 1…2 (M6)
2…14 Int16 Reserved Reserved for future use. 0 0