PowerMonitor 5000 Unit Data Tables Appendix A
Configuration.TriggerSetpointInfoFile (M6 model)
Configuration.TriggerData(M6 model)
Table 89 - Table Properties
CIP Instance Number 865
PCCC File Number ST74
No. of Elements 1
Length in Words 32
Data Type String
Data Access Write Only
Table 90 - Configuration.TriggerSetpointInfoFile Data Table
Element
Number
Type Tag Name Description Default Range
0 String Trigger_Setpoio
nt_Log_File
A single entry table for a 64 character Filename entry 0 64 bytes
Table 91 - Table Properties
CIP Instance Number 822
PCCC File Number N31
No. of Elements 10
Length in Words 10
Data Type Int16
Data Access Read/Write
Table 92 - Configuration.TriggerData Data Table
Element
Number
Type Tag Name Description Default Range
0 Int16 Trigger_Mode Selects how records are saved. 0= Fill and stop recording when log is full. 1= Overwrite
when log is full starting with the earliest record.
101
1 Int16 TriggerData_Length_s TriggerData log length from 1s to 10s 1s 1…10s
2 Int16 TriggerData_Parameter_1 Selection of parameter or default to be logged in the trigger data log. 5 1…184
3 Int16 TriggerData_Parameter_2 9 1…184
4 Int16 TriggerData_Parameter_3 14 1…184
5 Int16 TriggerData_Parameter_4 15 1…184
6 Int16 TriggerData_Parameter_5 19 1…184
7 Int16 TriggerData_Parameter_6 23 1…184
8 Int16 TriggerData_Parameter_7 27 1…184
9 Int16 TriggerData_Parameter_8 39 1…184