Appendix A PowerMonitor 5000 Unit Data Tables
Configuration.OptionalComm.DNT
Table 79 - Table Properties
CIP Instance Number 816
PCCC File Number N25
No. of Elements 30
Length in Words 30
Data Type Int16
Data Access Read/Write
Table 80 - Configuration.OptionalComm.DNT Data Table
Element Number Type Tag Name Description Default Range
0 Int16 DeviceNet_Address DeviceNet optional card device address 63 0…63
1 Int16 DeviceNet_Baudrate DeviceNet optional card communication rate.
0 - 125k
1 - 250k
2 - 500k
3 - AutoBaud
30…3