PowerMonitor 5000 Unit Data Tables Appendix A
23 Real IEEE1159_Voltage_Imbalance_Limit_% The percent of voltage Imbalance to create an imbalance event 3 1.00…10.00
24 Real IEEE1159_Current_Imbalance_Limit_% The percent of current Imbalance to create an imbalance event 25 1.00…50.00
25 Real IEEE1159_DCOffset_Harmonic_Avg_Intvl_m The a rolling average interval for DC offset and Harmonics in
minutes
5 1…15
26 Real IEEE1159_Voltage_DCOffset_Limit_% The percent of DC offset limitation 0.1 0.00…1.00
27 Real IEEE1159_Voltage_THD_Limit_% The percent of voltage THD limitation 5 0.00…20.00
28 Real IEEE1159_Current_THD_Limit_% The percent of current THD limitation 10 0.00…20.00
29 Real IEEE1159_PowerFrequency_Avg_Intvl_s The rolling average interval for power frequency in seconds. 1 1…10
30 Real IEEE1159_PowerFrequency_Limit_Hz The limitation on power frequency variation in Hz. 0.1 0.1…0.2
31 Real IEEE1159_PowerFrequency_Hysteresis_Hz Hysteresis of power frequency 0.02 0.01…0.05
32 Real IEEE519_Compliance_Parameter IEEE 519 Compliance Parameter
0 = Current
1= Voltage
00…1
33 Real IEEE519_MAX_Isc_Amps Short circuit current available at the point of common coupling.
(PCC) IMPORTANT: When Isc is ‘0’ or IL is ‘0’, the first row in IEEE 519
Current Distortion Limits table is selected for compliance.
0 0.00…1,000,000.0
0
34 Real IEEE 519 MAX_IL_Amps Average maximum demand for current for the preceding 12
months. IMPORTANT: When IL is ‘0’ the current THD instead of TDD is
used for compliance.
0 0.00…1,000,000.0
0
35 … 49 Real Reserved Reserved for future use. 0 0
Table 78 - Configuration.PowerQuality Data Table
Element
Number
Type Tag Name Description Default Range