Manual

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 279
PowerMonitor 5000 Unit Data Tables Appendix A
Configuration.Data_Log
Table 73 - Table Properties
CIP Instance Number 813
PCCC File Number N22
No. of Elements 34
Length in Words 34
Data Type Int16
Data Access Read/Write
Table 74 - Configuration.Data_Log Data Table
Element
Number
Type Tag Name
(default tag name)
Description Default Range
0 Int16 Data_Logging_Interval Logging Interval in seconds.
0=Disables data logging
-1= synchronize log with demand period
900 (15 min) -1…3600
1 Int16 Logging Mode Selects how records are saved.
0= Fill and stop recording when log is full
1= Overwrite when log is full starting with the earliest record.
101
2 Int16 DataLog_Parameter_1
(Avg_V_N_Volts)
Selection of parameter or default to be logged in the data log. 5 0…88 (M5)
1…184 (M6)
3 Int16 DataLog_Parameter_2
(Avg_VL_VL_Volts)
Selection of parameter or default to be logged in the data log. 9 0…88 (M5)
1…184 (M6)
4 Int16 DataLog_Parameter_3
(Avg_Amps)
Selection of parameter or default to be logged in the data log. 14 0…88 (M5)
1…184 (M6)
5 Int16 DataLog_Parameter_4
(Avg_Frequency_Hz)
Selection of parameter or default to be logged in the data log. 15 0…88 (M5)
1…184 (M6)
6 Int16 DataLog_Parameter_5
(Total_kW)
Selection of parameter or default to be logged in the data log. 19 0…88 (M5)
1…184 (M6)
7 Int16 DataLog_Parameter_6
(Total_kVAR)
Selection of parameter or default to be logged in the data log. 23 0…88 (M5)
1…184 (M6)
8 Int16 DataLog_Parameter_7
(Total_kVA)
Selection of parameter or default to be logged in the data log. 27 0…88 (M5)
1…184 (M6)
9 Int16 DataLog_Parameter_8
(Total_PF_Lead_Lag_Indicator)
Selection of parameter or default to be logged in the data log. 39 0…88 (M5)
1…184 (M6)
10 Int16 DataLog_Parameter_9
(Avg_True_PF)
Selection of parameter or default to be logged in the data log. 31 0…88 (M5)
1…184 (M6)
11 Int16 DataLog_Parameter_10
(Avg_Disp_PF)
Selection of parameter or default to be logged in the data log. 35 0…88 (M5)
1…184 (M6)
12 Int16 DataLog_Parameter_11
(Avg_IEEE_THD_V_%)
Selection of parameter or default to be logged in the data log. 54 0…88 (M5)
1…184 (M6)
13 Int16 DataLog_Parameter_12
(Avg_IEEE_THD_V_V_%)
Selection of parameter or default to be logged in the data log. 58 0…88 (M5)
1…184 (M6)
14 Int16 DataLog_Parameter_13
(Avg_IEEE_THD_I_%)
Selection of parameter or default to be logged in the data log. 63 0…88 (M5)
1…184 (M6)
15 Int16 DataLog_Parameter_14
(Avg_IEC_THD_V_%)
Selection of parameter or default to be logged in the data log. 68 0…88 (M5)
1…184 (M6)